Skip to main content

Thermodynamics · Response functions and stability

Refrigerant-134a is compressed in a steadily operating adiabatic compressor of a…

Problem

Refrigerant-134a is compressed in a steadily operating adiabatic compressor of a vapor-compression refrigerator from a saturated-vapor inlet at −8 °C, where \(h_1=242.54\,\mathrm{kJ/kg}\), \(s_1=0.9377\,\mathrm{kJ/kg\cdot K}\) and \(v_1=0.09193\,\mathrm{m^3/kg}\), to a condenser pressure of \(1.200\,\mathrm{MPa}\). If the compression were internally reversible, the exit enthalpy would be \(h_{2s}=287.10\,\mathrm{kJ/kg}\). The actual compressor isentropic efficiency, defined as \((h_{2s}-h_1)/(h_2-h_1)\), is \(0.80\). Saturated liquid leaves the condenser at \(1.200\,\mathrm{MPa}\) with \(h_3=117.77\,\mathrm{kJ/kg}\) and is throttled isenthalpically into the evaporator. Kinetic and potential energy changes are negligible. The measured refrigeration capacity is \(45.0\,\mathrm{kW}\). Determine (a) the actual compressor-exit enthalpy, (b) the refrigerant mass flow rate, (c) the actual compressor power, (d) the condenser heat-rejection rate, and (e) the actual COP. Also compute the COP that would be obtained if the compressor were isentropic, using the same mass flow rate and the same condenser-exit and evaporator-inlet enthalpies.

Hint

\(\eta_s\) stretches the isentropic enthalpy rise into a larger actual rise; \(q_L\) still uses the evaporator enthalpies only.

Check your work

Work the problem yourself first. Then open it in Training to check your answer and read the full worked solution.

The answer check and full solution for this problem come with ProofAnvil Practice membership ($19 USD monthly). See membership. Or start with the free Thermodynamics sample problem: Try the free sample problem.

More Thermodynamics practice problems

Back to Thermodynamics

An original ProofAnvil practice problem, written for this course. ProofAnvil is a practice course, not a homework-answer service.